Shopping Cart

Your cart is empty.

Your cart is empty.

Power Quality Analyzer Meter 3 Phase Power Energy Analyzer with 4 PCS Flexible Coil Current Sensor Current Range 10A~6000A

Free shipping on orders over $29.99

$2,840.00

$ 99 .00 $99.00

In Stock

About this item

  • ◆ ◆ Package with 4PCS Flexible Coil Current Sensors size Φ300mm;Range 10A~6000A;
  • ◆ Analysis and diagnosis of all voltage parameters such as voltage, current, power, energy, harmonics, and phase.
  • ◆ 4-channel current and voltage measurement, while capturing and recording power parameters and waveforms; Line voltage:Below 600V
  • ◆ Multifunctiondisplay: Transient capture function; Starting current monitoring; Trend chart recording and storing function; Alarm function; Snapshot function; Setting function
  • ◆ The Power Quality Analyzer is a versatile, intelligent and comprehensive test instrument designed to test three-phase power quality in the field. It has the characteristics of simple man-machine operation, easy to use, large LCD color screen display, high resolution, anti-vibration structure and other features.



Product Description

1

Power Quality Analyzer's Basic Function:

  • Test function:

Real-time waveform display (4-channel voltage/4-channel current); true RMS voltage and current; voltage DC component; current and voltage peak value; maximum/minimum value of current and voltage within a period of time; phasor diagram display; each phase Harmonic measurement, up to the 50th harmonic; bar graph showing the harmonic ratio of current and voltage of each phase; calculation of total harmonic distortion (THD); active/reactive/apparent power value and total value of each phase ; Active/reactive/apparent energy value and total value of each phase; transformer K factor calculation; COSφ displacement power factor (DPF) and power factor (PF) calculation; flicker calculation; three-phase unbalance calculation (voltage and current )

  • Transient capture function

Monitoring instantaneous change of power grid voltage current parameters, including the voltage current fluctu-ations, voltage current surge, sag and short supply interruption, temporary overvoltage, impact current and Cur-rent voltage instantaneous distortion. Instruments can store 150 sets of transient waveform at the same time.

  • Starting current monitoring

Monitoring surge current of line and the startup current when electrical equipment is starting, help to correctly design capacity. Can be display the RMS rising / falling curve In the startup process, the envelope curve of startup current, waveform of 4 channels current and 4 channels voltage. Recording about 100s after trigger, storage the current /voltage instantaneous and waveform curve of each cycle in 100s.

  • Trend chart recording and storing function

Store all the test parameters of basic test functions (Urms, Uthd, Ucf, Uunb, Hz, Vrms, Vthd, Vcf, Vunb, PST, Arms, Athd, Acf, Aunb, KF,W, VAR, VA, PF, COSφ, TANφ),50 voltage harmonics, 50 current harmonics. And create the trend curve. Record data for a long time according to need(concurrent selection 20 parameters to record data for once every five seconds, you can record about 300 days.).

  • Alarm function

Set the limit values according to need, monitoring the values whether overshoot, if overshoot will generate an alarm log, such as: voltage, current, unbalance, harmonic ratio, frequency, active power, total harmonic distor-tion. You can configure 40 different alarms, each group can set different monitoring parameters (including 50 harmonics, total of 123 different parameters) and limit values, also can set the shortest time of overshoot. The log can contain up to 12,800 alarms.

  • Snapshot function

Any screen can be saved (screen snapshot), at the same time automatically records the time and test mode. Such as can save voltage and current waveform, harmonic bar chart, phasor diagram etc. It can save a maximum of 60 screen snapshot.

  • Communication function

Communicate with computer via USB; Monitoring software can display waveform of power quality analysis, read of the transient waveform, trend chart recording, alarm log, screenshots, and display on the computer.

  • Setting function

The user can configuration of the time and date, configuration of the screen contrast and brightness, definition of each phase curve colors’.

Choice of type of connection to the net work.

Configuration of the type of the current sensors and voltage ratios.

Select Chinese menu or English menu.

  • Help menu in Chinese/English

Every stage of operation can press the "help" key to obtain relevant information.

Technical Specifications

  • Power supply: Rechargeable lithium-ion battery packs 9.6V, backup charger.
  • Battery indicator: Battery symbol shows dump energy. When the voltage is too low, automatic shutdown after the 1 minute.
  • Power consumption: Current consumption of normal test 490 mA, continuous working for 8 hours.
  • Display mode: LCD color screen, 640dots×480dots, 5.6 inches, display domain: 116mm×88mm.
  • Size of clamp: 6000A Flexible Coil Current Sensor (with Integrator): Φ300mm,(Range:10A~6000A)
  • Instrument dimensions: L×W×H: 240mm×170mm×68 mm
  • Number of channels: 4U/4I.
  • Phase-to phase voltage: 1.0V~2000V.
  • Phase-to-neutral voltage : 1.0V~1000V.
  • Current: 6000A current clamp: 10A~6000A;
  • Frequency: 40Hz~70Hz.
  • Parameters of electricity: W, VA, Var, PF, DPF, cosφ, tanφ.
  • Energy parameters: Wh, Varh, Vah
  • Harmonic: Order 0~50.
  • Total harmonic distortion: Order 0~50, each phase.
  • Expert mode: Yes.
  • Number of Transient records: 150 sets.
  • Voltage flicker: Yes.
  • Starting current mode: Yes, 100 seconds.
  • 3 phases unbalance: Yes
  • Record: 300 days(simultaneous recording 20 parameters, record one point every 5 seconds).
  • Min/Max recorded value: Measurement of maximum and minimum values over a period of time.
  • Alarm: 40 different types of parameter selections, 12,800 sets alarm logs.
  • Peak: Yes.
  • Phasor diagram display: Automatically.
  • Capacity of snapshots: 60
  • Menu language: English/Chinese.
  • Communication: USB.
  • Automatic switching off: When an alarm campaign is initiated or a search for transients, an inrush current capture, or a trend recording is pending or in progress, the device is not automatic switching off.

  • In other test mode, 15 minutes without keystrokes, automatic shutdown after prompt 1 minute.
  • Backlight function: Yes, suitable for use at night and dark place.
  • Weight: Host: 1.6kg (with battery).6000A Flexible Coil Current Sensor (with Integrator): 330g×4;Test wires and power adapter: 900g; Total weight: about 9.2kg (with packaging).
  • Length of voltage test wire: 3m.
  • Length of current sensor wire: 2m.
  • Working temperature and humidity: -10°C~40°C; below 80%Rh.
  • Storage temperature and humidity: -10°C~60°C; below 70%Rh.
  • Input impedance: Input impedance of test voltage: 1MΩ.
  • Withstand voltage: Withstand 3700V/50Hz sinusoidal AC voltage for 1 minute between instrument wiring and shell.
  • Insulation: Between instrument wiring and shell ≥10MΩ.
  • Structure: Double insulation, with insulation vibration-proof sheath.
  • Safely rules: IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.